Do you know what the alarm means?
Jul 14, 2022, 10:11 am My probe is new. I did the change and recalibration procedure. Everything works perfectly. It is the device that goes into alarm. I don't know what Alarm means |
Olivier Michaud Jul 14, 2022, 10:12 am Take the test you never know |
Olivier Michaud Jul 14, 2022, 10:13 am Normally in tap water you should have seen a value between 6.5 and 7.5 |
Jul 14, 2022, 10:13 am I will do it. THANKS |
Olivier Michaud Jul 14, 2022, 10:13 am With vinegar 4 or 5 |
Jul 14, 2022, 10:14 am in the glass of water: 7.1 |
Olivier Michaud Jul 14, 2022, 10:14 am 0k |
Jul 14, 2022, 10:14 am in vinegar: 5.2 |
Olivier Michaud Jul 14, 2022, 10:15 am When the probe is in a glass of water, does the pump run? |
Jul 14, 2022, 10:16 am I ran the pump by plugging the probe socket |
Olivier Michaud Jul 14, 2022, 10:17 am Do this, put the probe in a glass of water and add lye. The ph should rise and the pump should start |
Jul 14, 2022, 10:19 am the pump is triggered as soon as the pH reaches 7.6. But after an hour, the device goes into Alarm and I have to press the V button to restart. |
Olivier Michaud Jul 14, 2022, 10:19 am Do you work with pH minus? |
Jul 14, 2022, 10:19 am yes PH Less |
Olivier Michaud Jul 14, 2022, 10:20 am And after an hour the ph is at what value? |
Olivier Michaud Jul 14, 2022, 10:21 am The alarm that goes off prevents the device from emptying your ph minus tank, this is normal |
Jul 14, 2022, 10:22 am the pump runs for a few minutes and stops. At the end of the day, I found the device in alarm and the Ph rose by 0.1. |
Olivier Michaud Jul 14, 2022, 10:24 am Do this: put the probe in a glass of water with washing powder. |
Olivier Michaud Jul 14, 2022, 10:26 am Take out the pH minus hose! |
Jul 14, 2022, 10:27 am the distribution of ph minus has been triggered. I take out the pipe? This will send air? |
Olivier Michaud Jul 14, 2022, 10:28 am It doesn't matter, it's just to avoid emptying your canister of ph |
Jul 14, 2022, 10:29 am and now what should i do |
Olivier Michaud Jul 14, 2022, 10:30 am The probe is in a glass of water and with detergent? |
Jul 14, 2022, 10:31 am Yes |
Olivier Michaud Jul 14, 2022, 10:31 am Should the pump be running? |
Jul 14, 2022, 10:31 am Yes |
Olivier Michaud Jul 14, 2022, 10:32 am Let it run for 10 minutes (to see if the alarm goes off) |
Oivier Michaud Jul 14, 2022, 10:32 am And then add vinegar to the glass the ph should go down and the pump will stop |
Jul 14, 2022, 10:33 am I do it and I will contact you |
Olivier Michaud Jul 14, 2022, 10:33 am Yes |
Jul 14, 2022, 11:09 am The device did not go into alarm after 10 minutes. It is rather after about 1 hour of restarting. I have lost the user manual where there are no doubt the explanations. I try to get it. Thanks for your help. Cordially |
Olivier Michaud Jul 14, 2022, 11:10 am Has the pump run for 10 minutes? |
Jul 14, 2022, 11:10 am No, the pump stopped after a few minutes, I did not time |
Olivier Michaud Jul 14, 2022, 11:11 am And what pH value could you read? |
Jul 14, 2022, 11:11 am 7.9 |
Olivier Michaud Jul 14, 2022, 11:13 am While the pump is running add vinegar and see if this stops the pump (pH <7.6 |
Jul 14, 2022, 11:13 am I did it earlier, it was OK |
Olivier Michaud Jul 14, 2022, 11:14 am Does the pump stop? |
Jul 14, 2022, 11:15 am yes, the pump stops. During the day when I go to see, I find the device in alarm. I will try to stay watching when this happens. Thank you for your help. Good day |
Olivier Michaud Jul 14, 2022, 11:16 am Probably because the injection of pH is not enough to lower the pH sufficiently. Have a good day |
Jul 14, 2022, 11:16 am I will come back to you when I have timed everything. THANKS |
|